UltraLITE Model ELC (600W to 2kW) Single Phase
The UltraLITE Model ELC’s compact front access design features one of the smallest cabinet footprints in the industry!
Meeting the NFPA 101 and NFPA 111 standards, the Model ELC is considered “Life Safety Equipment.” It is also UL 924 listed as “Emergency Lighting Equipment,” providing the required 90 minutes of emergency backup power, and is 100% compatible with all lighting applications and life safety systems. The Model ELC’s voltage regulation and performance characteristics extend ballast, LED driver, and lamp life, which make this product an advantageous choice over competing lighting inverters.
Whether fed from the AC power source or even while in battery mode, the ELC has a peak overload capability of 1200% to accommodate inrush current from LED fixtures!
- Automatic self-testing, data logging, and reporting per NFPA 101 – 7.9.3.1.3.
- Uninterrupted, regulated, continuous sine wave output for use with “normally on” lighting fixtures and exit lamps, LED and HID compatible
- Standby output for use with “normally off” emergency lighting fixtures
- Timed Normally Off Bus “PLUS” option includes an adjustable soft start to accommodate the high inrush current of “normally off” emergency lights.
- True, online double-conversion topology provides conditioned, regulated power and 100% reliability to emergency lighting loads
- High-speed automatic static bypass
- Manual bypass switch
- Advanced DSP control used for enhanced performance, accuracy, and system reliability
- Standard NEMA 2 drip-proof enclosure
- One (1) Output Circuit Breaker included for the “Normally On” bus and/or the “Timed Normally Off” bus.
- A total of (12) circuit breakers or (6) monitored circuit breakers are available (120V or 277V), and can be factory-wired to the “Normally On” bus and/or optional “Normally Off” bus, in any combination specified.
- Generator compatible
- 4-stage, temperature-compensated battery charger for increased battery life
- An industry-leading battery recharge time of 24 hours or better
- Optional NetMinder Ethernet/MODBUS/BACnet adapter for remote monitorin
- Input Operating Voltage Range: +12%, -30% typical, load-dependent, without battery usage; +12%, -15% at full load
- Input Frequency: 60 Hz, ± 2.5%
- Input Current Harmonic Distortion: < 5% THD
- Input Power Factor Correction: > .97 pF at full load
- Output Sine Wave Voltage: Typically 3% output THD with linear load
- Output Regulation: Typically better than ± 2%
- Overload: Up to 125% for 30 cycles, 150% for 4 cycles when fed from the AC power source, or on battery (without use of static bypass)
- LED Inrush Rating: Peak overload capability of 1200% to accommodate inrush current from LED fixtures (without the use of static bypass)
- Operating Temperature: 20º to 35º C (for “UL 924 Emergency Lighting Equipment” Listed models); Optimum battery performance and life at 25º C
- Operating Temperature: 0º to 40º C (for “UL 924 Auxiliary Lighting and Power Equipment” Listed models); Optimum battery performance and life at 25º C
- Operating Temperature: 10º to 40º C (for models that are C-UL Listed to CSA C22.2 No. 141-02); Optimum battery performance and life at 25º C
- Inverter electronics designed for use at 0º to 40º C
- Battery Time: UL 924 Listed 90 minutes at full-rated kW output, or with optional run times from 15 minutes to 4 hours, C-UL Listed to CSA C22.2 No. 141-02 with 30 minutes run time
- Audible Noise: < 50 dB
Brochures and Data Sheets
Specifications
White Papers
- Multiple Voltage Capabilities
- UL924 Auxiliary Lighting and Power
- Remote Input Command
- Zone Sensing
- Local Control Override
- Egress Lighting Integrity Test
- Advanced Remote Monitoring
- Advanced Remote Monitoring MODBUS
- Advanced Remote Monitoring BACnet
- Emergency Ballasts or Centralized Inverter
- Design Flexibility of Inverters
- Critical Healthcare Environments